Show simple item record

dc.contributor.advisorNatarajan, Krishnamoorthy
dc.contributor.authorDoan, Robert E.
dc.date.accessioned2017-06-07T20:07:51Z
dc.date.available2017-06-07T20:07:51Z
dc.date.created1999
dc.date.issued1999
dc.identifier.urihttp://knowledgecommons.lakeheadu.ca/handle/2453/3101
dc.description.abstractThis thesis examines a specific problem of governor control on a set of hydroelectric turbines that suffer from severe wicket gate leakage. Linear modeling and the steady state behavior of each turbine is investigated and used to determine the best means of speed control. Findings show that a secondary water control device may be used with the wicket gates to alleviate the effects o f leakage while the generator is disconnected from the transmission system. The control method results in two distinct modes of turbine operation, with each having significantly different dynamic characteristics. A digital speed droop governor scheme is considered in a gain scheduling arrangement to account for the two operating modes. The stability boundaries of the governor parameters are investigated, and an output feedback cost minimization algorithm is used for obtaining controller gains. An outline of the software used to implement the governor on an industrial programmable controller is presented, and the experimental performance for the turbines is compared to the theoretically developed model.
dc.language.isoen_US
dc.subjectGovernors (Machinery)
dc.subjectHydroelectric power plants Ontario Kakabeka Falls Automatic control
dc.titleGovernor control for Kakabeka Falls Generating Station
dc.typeThesis
etd.degree.nameMaster of Science
etd.degree.levelMaster
etd.degree.disciplineEngineering : Control
etd.degree.grantorLakehead University


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record